Parameter sets: Wide-spectrum smoke detector
4.4.2
4.4.2.1
4.4.2.2
No. Name
Risk of injury to
persons
small...
large
2
Standard
3
Standard Plus
4.4.2.3
60
Building Technologies
Fire Safety
Wide-spectrum smoke detector FDO221
Description
Standard (2):
The priority of the 'Standard' parameter set is set to robust response. It is therefore
particularly suited to use in rooms with few deceptive phenomena such as cigarette
smoke.
Standard Plus (3):
This parameter set is both fast and sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.
Use
Concentration
of valuable
items
low...
high
Specification
No.
Name
2
Standard
3
Standard Plus
All parameter sets meet the criteria of standard EN 54-7.
Room
Deceptive
geometry
phenomena
simple...
few...
complex
many
Response time [s]
60
50
Risk of fire
Critical fire size
small...
small...
large
medium
Sensitivity [%/m]
2,8
2
007004_n_en_--
01.07.2012