3.4.8
3.4.9
Building Technologies
Fire Safety
Renovation mode
When operating the point detectors on the FDnet, individual detectors can be set
specifically to renovation mode on the control panel.
Select renovation mode if major work is being carried out in the room and large
volumes of dust or aerosols are being produced.
NOTICE
Changed settings
Limited alarm functions in renovation mode.
In renovation mode, the neural fire detector and the heat detector only trigger
an alarm when the temperature exceeds 80 °C for 20 seconds.
The wide-spectrum smoke detector does not trigger an alarm in renovation
mode. All other functions continue to work as normal.
Test mode
For testing purposes the point detectors can be set to test mode. In test mode the
point detectors react faster and with a higher sensitivity level.
Electronic testing:
The point detectors can be tested with the detector exchanger and tester FDUD292
or the intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.
Physical testing:
The optical function part on the neural fire detector can also be tested with the
test gas REF8 or REF8-S.
The heat sensors of the neural fire detector can be tested with:
–
Hot air fan
–
RE6T detector tester for heat detectors
–
RE7T Solo461 heat detector tester kit
See also
Testing detectors [
Applicable documents [
Structure and function
Function
111]
9]
3
37
007004_n_en_--
01.07.2012