4 Planning

4.1 Compatibility

4.2 Ambient features

Building Technologies
Fire Safety
Compatible with control panels that support the FDnet detector line.
Neural fire detectors can also be operated as follows:
FDOOT241-A3 on AnalogPLUS
FDOOT241-A4 on SIGMALOOP
FDOOT241-9 and FDOOT241-A9 on a collective detector line
FDOOT241-8 on an MS8 detector line
You will find details in the 'List of compatibility'.
See also
Applicable documents [
In selecting the optimum parameter set, the following factors must be taken into
account:
Risk of injury to persons
Concentration of valuable items
Room geometry
Deceptive phenomena
Risk of fire
Critical fire size
Risk of injury to persons
People's lives are severely at risk in venues such as concert halls, nursing homes,
and hospitals. The risk of injury to persons is therefore very high in such places. In
canteen kitchens the situation is different. Few people work in such facilities and
are able to save themselves in the event of timely alarms. The risk of injury to
persons is thus rather low in this case.
Concentration of valuable items
Irreplaceable cultural assets are often on display in museums. Computer centers
house servers with large data volumes. The concentration of valuable items is
rather high. In a normal hotel room the concentration of valuable items must be
classified as low.
Room geometry
High ceilings, complex room shapes or well ventilated rooms have a complex room
geometry. This aggravates early fire detection, as it is difficult for the fire
phenomenon to reach the fire detector. An office room with normal ceiling height
has a simple room geometry.
Planning
Compatibility
9]
007004_n_en_--