4.5 Parameter sets: Heat detector

4.5.1
4.5.1.1
Building Technologies
Fire Safety

Heat detector FDT241

Description

The heat detector FDT241 has the following parameter sets:
A1R (1)
BR (2)
A1S (3)
BS (4)
Download 1 (14) / Download 2 (15)
Application-specific parameter sets that can be loaded on-site (depending on
the control panel).
Notes on the designations A1 and B
A1 parameter sets should be operated at a room temperature of around 25 °C.
However, they can be applied at temperatures up to 50 °C. The static response
temperature is 60 °C.
B parameter sets are normally operated at around 40 °C. They can however be
used at up to 65 °C. The static response temperature is 80° C.
Notes on the designations R and S
Compared with S parameter sets, R parameter sets also trigger an alarm when the
temperature increases (e.g. from 20 °C to 50 °C within a few minutes).
Planning
Parameter sets: Heat detector