Neural fire detector FDOOT221

Description

Standard (2):
The priority of the 'Standard' parameter set is set to robust response. It is thus
particularly suited to application in rooms where deceptive phenomena such as
cigarette smoke or dust can be expected.
Standard Plus (4):
This parameter set is fast and highly sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.

Use

Concentration of
Room geometry
valuable items
low...
simple...
high
complex

Specification

Sensitivity, open
Sensitivity,
fire
smoldering fire
[%/m]
[%/m]
3,2
11,4
2,3
8
Applicable with fast temperature increases > 10 K/min.
1
All parameter sets meet the criteria of standard EN 54-7.
Parameter sets: Neural fire detector
Deceptive
Risk of fire
phenomena
few...
small...
many
large
Thermal
Static activation
Differential activation
temperature
temperature
[°C]
T [K]
80
29
80
25
Planning
4
Critical fire size
small...
medium
1
57
007004_n_en_--