Setting name
DNP3 Destination
Address
DNP3 Application
Timeout
*Not applicable for RS485 or RS232 interface modules.
**Fibre Optic Module only
2.1.8

Connecting to the Relay via Reydisp

When Reydisp software is running all available communication ports of the PC will automatically be detected.
On the start page tool bar open up the sub-menu File > Connect.
The 'Communication Manager' window will display all available communication ports. With the preferred port
highlighted, select the 'Properties' option and ensure the baud rate and parity match that selected in the relay
Data Comms settings. Select 'Connect' to initiate the relay-PC connection.
Via the Relay > Set Address > Address set the relay address (1-254) or alternatively search for connected
devices using the Relay > Set Address > Device Map. The relay can now be configured using the Reydisp
software. Please refer to the Reydisp Evolution Manual for further guidance.
©2015 Siemens Protection Devices Limited
Chapter 2) 7SR242 Duobias Settings, Configuration & Instruments Guide
Range
0 ... 65534
5, 6 ... 299, 300
Figure 2-5
PC Comms Port Allocation
Default
Units
0
10s
Seconds
Notes
Setting is only visible when
a port protocol is set to
DNP3.
Setting is only visible when
a port Protocol is set to
DNP3
Chapter 2 Page 22 of 22