Reactor, Motor And Connections Protection - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

6.6 Reactor, Motor and Connections Protection

Fig. 6-10 AC Connections for Reactor and Connections Protection
Settings must take into consideration:
Connections: High internal and through fault currents.
Series reactor: Through fault current limited by reactor.
Shunt reactor: Single end fed faults only.
Motor: Single end fed faults only.
Generator: Single end fed faults only.
Primary current values are not subject to variation due to tap changing (as in transformer / OLTC applications),
st
the 87BD and 87BD 1
Bias Slope can both be set to 0.1.
The inrush inhibit feature (81HBL2) must be enabled as the magnetising inrush currents in each phase will not
balance.
©2015 Siemens Protection Devices Limited
Chapter 7 Page 58 of 64

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents