27/59 Under/Over Voltage; Reference; Operate And Reset Level; Operate And Reset Time - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

2.2

27/59 Under/Over Voltage

2.2.1

Reference

Parameter
V
Setting
s
hyst
Hysteresis setting
t
Delay setting
d
2.2.2

Operate and Reset Level

Attribute
V
Operate level
op
Reset level
Repeatability
Variation
2.2.3

Operate and Reset Time

Attribute
Element basic
t
basicE
operate time
t
Operate time following delay
op
Repeatability
Disengaging time
©2015 Siemens Protection Devices Limited
Overvoltage
Undervoltage
-10 °C to +55 °C
f
- 3 Hz to f
+ 2 Hz
nom
nom
Overvoltage
Undervoltage
Chapter 3) 7SR242 Duobias Performance Specification
Value
5, 5.5...200V
0, 0.1... 80.0%
0.00, 0.01...20.00, 20.50... 100, 101... 1000, 1010...
10000, 10100... 14400 s
Value
100 % Vs,
1 % or 0.25V
= (100 % - hyst) x V
1 %
op,
= (100 % + hyst) x V
op,
1 %
5 %
5 %
Value
0 to 1.1 x Vs: 73 ms
10ms
0 to 2.0 xVs: 63 ms
10ms
1.1 to 0.5 xVs: 58 ms
10ms
t
+ t
,
1 % or
10ms
basic
d
1 % or
10ms
< 80 ms
1 %
Chapter 3 Page 21 of 50