Time Delayed Derived Earth Fault; Reference; Operate And Reset Level - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

2.11 51N Time Delayed Derived Earth Fault

2.11.1 Reference

Parameter
Is
Setting
char
Characteristic setting
Tm
Time Multiplier setting
t
Delay setting
d
t
Reset setting
res

2.11.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Variation
©2015 Siemens Protection Devices Limited
-10 °C to +55 °C
f
- 3 Hz to f
+ 2 Hz
nom
nom
Chapter 3) 7SR242 Duobias Performance Specification
Value
0.05, 0.1... 2.5 xIn
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
0.025, 0.030... 1.6, 1.7... 5, 6... 100
0, 0.01... 20 s
ANSI DECAYING, 0, 1... 60 s
Value
105 % Is,
4 % or
1% In
95 % I
op
1 %
5 %
5 %
Chapter 3 Page 33 of 50