2.17 87HS High-Set Differential

2.17.1 Reference

Parameter
ICT
Multiplier
Is
Setting
ts
Delay setting

2.17.2 Operate and Reset Level

Attribute
I
Operate level
op
Reset level
Repeatability
Transient overreach
Variation

2.17.3 Operate and Reset Time

Attribute
Element basic operate time
t
basic
Switched from 0 to x I
t
Operate time following delay
op
©2015 Siemens Protection Devices Limited
-10 °C to +55 °C
f
- 3 Hz to f
+ 2 Hz
nom
nom
OP
Chapter 3) 7SR242 Duobias Performance Specification
Value
1.00x
1, 2 ... 30 xIn
0, 0.005... 1s
Value
5% of setting or
0.01In
95% of I
OP
2%
5%
Value
3 x I
, 30 ms,
10ms
OP
5 x I
, 25 ms,
10ms
OP
t
+ t
,
1% or
10ms
basic
d
Chapter 3 Page 46 of 50