Undercurrent (37, 37G); 37-N Elements - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

2.7

Undercurrent (37, 37G)

Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
2.7.1

37-n Elements

If two Undercurrent 37 elements are used with different settings, it is convenient to test the element with the
lowest setting first. The higher setting element can then be tested without interference from the other element.
These elements can be allocated to W1 or W2 current inputs by relay settings, ensure that current is injected on
the correct input.
Apply 3P balanced current at a level above the 37-n setting until the element resets.
If DTL setting is small, gradually reduce any each phase current in turn until element operates.
If DTL is large apply 1.1x setting, check for no operation, apply 0.9x setting, check operation
Testing of these elements phase by phase may cause inadvertent operation of the 46 NPS Overcurrent elements.
Apply 0.5x setting current and record operating time
©2015 Siemens Protection Devices Limited
Chapter 6) 7SR242 Duobias Commissioning & Maintenance Guide
Figure 2-9 Undercurrent
n/a
W1-I
(I
), W1-I
(I
), W1-I
L1
A
L2
B
50N, 51N, 51G, 46, 87BD
37-n, 37G-n - Self Reset
(I
), I
or W2-I
(I
), W2-I
L3
C
G1
L1
A
(I
), W2-I
(I
), I
L2
B
L3
C
G2
Chapter 6 Page 37 of 62