Siemens 7SR242 Duobias Technical Manual page 322

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

Nomenclature
I
=
Fault current corresponding to the rated stability limit (primary Amps)
F
I
=
Maximum prospective internal fault current (primary Amps)
Fint
I
=
Secondary magnetising (exciting) current of current transformer at Vs volts.
MAG
I
=
Non-linear resistor (Metrosil) current.
NLR
Is =
Relay setting current
P.O.C. =
Primary operate current (fault setting)
R
=
Resistance of CT secondary winding.
CT
R
=
Resistance of CT connection leads
L
Rstab =
Resistance of stabilising resistor
T =
Turns ratio of all current transformers (Primary turns / Secondary turns)
V
=
Maximum secondary internal fault voltage
Fint
V
=
Kneepoint voltage of the CT
k
Vs =
Relay circuit setting voltage
©2015 Siemens Protection Devices Limited
Chapter 7 Page 6 of 64