Time Delayed Derived Earth Fault Protection (51N); Figure 3-8 Logic Diagram: Derived Time Delayed Earth Fault Protection - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

3.3.2 Time Delayed Derived Earth Fault Protection (51N)

Optionally two time delayed derived earth fault elements are provided, each can be selected to either winding 1 or
winding 2.
51N-n Setting sets the pick-up current level.
A number of shaped characteristics are provided. An inverse definite minimum time (IDMT) characteristic is
selected from IEC, ANSI or user defined curves using 51N-n Char. A time multiplier is applied to the
characteristic curves using the 51N-n Time Mult setting. Alternatively, a definite time lag delay (DTL) can be
chosen using 51N-n Char. When Delay (DTL) is selected the time multiplier is not applied and the 51N-n Delay
(DTL) setting is used instead.
The 51N-n Reset setting can apply a definite time delayed or ANSI (DECAYING) reset. The reset mode is
significant where the characteristic has reset before issuing a trip output – see 'Applications Guide'.
A minimum operate time for the characteristic can be set using the 51N-n Min. Operate Time setting.
A fixed additional operate time can be added to the characteristic using the 51N-n Follower DTL setting.
Operation of the time delayed earth fault elements can be inhibited from:
Inhibit 51N-n
51N-n Inrush Action: Inhibit
User Inhibit
Figure 3-8
©2015 Siemens Protection Devices Limited
A binary or virtual input.
Operation of the inrush detector function.
Reylogic (graphical logic).
Logic Diagram: Derived Time Delayed Earth Fault Protection
Chapter 1) 7SR242 Duobias Description Of Operation
Chapter 1 Page 31 of 60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents