87Hs; Figure 3-3 Differential Highset Characteristic - Siemens 7SR242 Duobias Technical Manual

Transformer protection relay
Hide thumbs Also See for 7SR242 Duobias:
Table of Contents

Advertisement

3.1.3 87HS

Figure 3.1-3 illustrates the differential highset characteristic. Within the relay the fundamental frequency RMS line
currents are modified by the ICT Multiplier and ICT Connection settings (see 3.1.1) before being applied to the
differential highset elements. The differential highset elements calculate the operate current for each phase from
the vector sum of winding 1 and winding 2 currents i.e. I
87HS Setting defines the differential current required to operate the element. The output of 87HS Delay can be
mapped to relay outputs.
Operation of the highset differential elements can be inhibited from:
Inhibit 87HS
87HS Inrush Action: Inhibit
87HS Overfluxing Action: Inhibit
User Inhibit
©2015 Siemens Protection Devices Limited
I
I
W1
W2
I
I
W1
W2
2
Figure 3-3
Differential Highset Characteristic
OPERATE
A binary or virtual input.
Operation of the inrush current detector
Operation of the overfluxing detector
Reylogic (graphical logic).
Chapter 1) 7SR242 Duobias Description Of Operation
= I
+ I
.
W1
W2
Chapter 1 Page 26 of 60