Mechanical Data - Kaco Powador 30.0 TL3 M/XL Operating Instructions Manual

Table of Contents

Advertisement

T echni ca l Dat a
4.2

Mechanical data

Display
Controls
Interfaces
Fault signal relay
AC connection terminals
AC cable connection
DC connection terminals (M variant)
DC connection terminals (XL variant)
Connections for DC cable connection
Connection for Ethernet cable connection
Ambient temperature range [°C]
Temperature monitoring
Cooling (free convection (K)/fan (L))
Protection rating according to EN 60529
Degree of contamination
DC disconnect
Housing
H x W x D [mm]
Total weight [kg]
Table 2:
Mechanical data
Operating Instructions Powador 30.0-39.0 TL3_EN
30.0 TL3 / 33.0 TL3 / 36.0 TL3 / 39.0 TL3
Graphical LCD, 3 LEDs
4-way button, 2 buttons
Ethernet, USB, RS485, S0
Potential-free NO contact, max. 30 V DC/1A or 230 V AC/1 A
Screw terminals inside the unit
min. cross section: 16 mm² rigid/fl exible
max. cross section: 50 mm² rigid/fl exible
Cable connection via M50 cable fi tting
Screw terminals on top hat rail inside the unit
min. cross section: 6 mm² rigid/fl exible
max. cross section: 35 mm² rigid/fl exible
Screw terminals on top hat rail inside the unit
min. cross section: 2.5 mm² rigid/fl exible
max. cross section: 10 mm² rigid/fl exible
Cable connection via 6 M32 cable fi ttings
Cable connection via M25 cable fi tting
-20 to 60
Steel plating
1360 x 840 x 355
yes
L
IP 54
PD2
Built-in
151
Page 15