Messages On The Display And The "Fault" Led - Kaco Powador 30.0 TL3 M/XL Operating Instructions Manual

Table of Contents

Advertisement

M a in tenance/Tro u b le s ho ot in g
9.5

Messages on the display and the "Fault" LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The triggering levels are
defi ned in standards, e.g. VDE0126-1-1. The inverter shuts down if the values exceed or fall below the approved levels.
9.5.1
Display of status and fault messages
Display
FS (fault status)
OS (operating status)
Details regarding the fault or operating status can be found either on the display or in the data that was recorded
through the RS485 interface.
9.5.2
Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work may only be carried out by an authorised electrician.
K = The indicated work may only be carried out by a service employee of KACO new energy GmbH.
Status
Display
OS 1
Waiting for feed-in
OS 2
Generator voltage
too low
OS 8
Self-test
FS
10
Temperature in
unit too high
OS 11
Measured values
FS
17
Shutting down
Powador-protect
Table 5:
Operating statuses and fault messages on the display
Operating Instructions Powador 30.0-39.0 TL3_EN
Fault LED (red)
ON
OFF
Explanation
Self-test: The grid parameters and
generator voltage are being checked.
Insuffi cient generator voltage and
power,
status before the transition to night
shutdown
Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode
In case of overheating, the inverter
switches off . Possible causes:
Ambient temperature too high
Fans covered
Inverter defect
Power limitation: If the generator power is too high, the inverter
limits itself to the maximum power (e.g. around noon if the generator
capacity is too large).
The activated grid and system
protection has been tripped.
Fault signal relay has switched.
Feed-in was ended due to a fault.
The fault signal relay deenergises again.
The inverter feeds back into the grid again after a
country-specifi c time period.
 Cool off the area
 Uncover the fans.
 Notify your
 Wait for reactivation.
 Notify your
Action
-
-
-
around the inverter.
authorised
electrician.
authorised
electrician if the
fault occurs several
times.