PR 5331A Manual page 21

2-wire programmable transmitter
Table of Contents

Advertisement

LERBAKKEN 10, 8410 RØNDE DENMARK.
FM Installation Drawing 5300Q502 Rev AH
Model 5331C,5331D, 5333C, 5333D and 5343B
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Model 5335C, 5335D, 5336D, 5337D
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Revision date:
2014-03-31
WWW.PRELECTRONICS.COM
1
2
6
3
5
4
SENSOR
1
2
6
3
5
4
SENSOR
Version Revision
V8R0
5 33 1 V 1 14 - UK
5300QF01
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected 
to any associated apparatus which 
uses or generates more than 250 
VRMS
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected 
to any associated apparatus which 
uses or generates more than 250 
VRMS
Doc. No.
5300Q502 Rev AH
Page:
1/2
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

5331d5333

Table of Contents