Modbus
7.5

Messages

Revised Jan-07
If you specify a zero address for a Modbus slave configuration, the
S600 configures the Modbus port using the address you enter here.
This is helpful when you load the same configuration file into multiple
S600s on the same Modbus address: each S600 then has a unique
node address.
To define the Modbus network addresses:
Select NETWORK SETUP from the Startup menu.
1.
Select MODBUS ADDRESS.
2.
Enter the address value (any value between 1 and 247). If you
3.
change the Modbus address, you must restart the S600 in order for
the change to take place.
During warm or cold starts the S600 can display various messages.
These include:
Message
REFLASH DISABLED
SECOND ETHERNET
CARD NOT PRESENT
INCOMPATIBLE PC
SETUP VERSION
NUMBER OF TOTALS
DOES NOT MATCH
CONFIGURATION
CHECKSUM
ERROR!
WARNING – FLASH
FILE SYSTEM
CORRUPT.
Startup
S600 Instruction Manual
Meaning
Firmware write protect is enabled.
To resolve: From the Cold Start menu,
select FACTORY SETUP > FIRMWARE
LOCK. You can then disable the firmware
write protect.
You are attempting to set up a second
Ethernet card which is not physically
installed.
To resolve: Install a dual Ethernet board,
if required
Note: Most applications do not need this
feature.
The configuration file has been edited
using a version of Config600 that is
incompatible with the version of firmware
on the S600.
To resolve: Identify and record the version
of software running on the S600 and the
version of Config600. Contact your support
centre for further directions.
You have initiated an S600 cold start with
a new config file that elects to keep totals.
To resolve: Cold start the S600 and select
RESET TOTALS.
Cold start has failed due to an invalid
checksum.
To resolve: Re-download the config file. If
the problem persists, contact your support
centre for further directions.
Flash file system has failed.
To resolve: Cold start the S600 and select
an S600 cold start.
7-5