4.1.5 Turbine Pulse Inputs

Figure 4-13. Pulse Input Schematic (with EU 12 V P148 Mezzanine Card)
Revised Jan-07
Table 4-7. DIGOUT Pin Connections for SKT-C
Pin
37
DIGOUT-CH3
36
DIGOUT-CH4
35
RETURN CH1-4
34
DIGOUT-CH5
33
DIGOUT-CH6
32
DIGOUT-CH7
31
DIGOUT-CH8
30
RETURN CH5-8
29
DIGOUT-CH9
28
DIGOUT-CH10
27
DIGOUT-CH11
26
DIGOUT-CH12
25
RETURN CH9-12
With the optional mezzanine card for pulse inputs (P148) installed, the
P144 I/O board supports four pulse inputs either independently or as
two pairs ("dual pulse mode"). Generally, the pulse inputs perform
dual pulse measurement, such as in turbine applications. In dual pulse
mode, you can enable level A or B pulse checking.
Each input has an input range of 1 to 10 KHz. Each channel has live
integrity checking. If cabling faults develop or if the pre-amp power
fails, the software activates a configurable circuit fail alarm.
The electrical connection for these inputs depends on which DPR
mezzanine card is fitted to the P144 I/O module. The dual mezzanine
card accepts pulse inputs from 3.5 Volts dc to 24 Volts dc, when wired
as show in Figures 4-13 and 4-14. It cannot accept NAMUR or current
mode preamps without external devices.
The P148 mezzanine card can interface to a variety of pre-amps,
including Spectra-Tek F106, Spectra-Tek IS106, Instromet MK15,
Faure Herman FH71 2-wire, Faure Herman FH71 3-wire, ITT Barton
818U, and Daniel 1838 Preamp.
Table 4-8 shows the dual pulse input pin connections.