Table 9-1 Class 1 - General Industrial; Table 9-2 Class 2 - Filtered Industrial - Siemens MICROMASTER 440 Series Operating Instructions Manual

Frequency inverters
Hide thumbs Also See for MICROMASTER 440 Series:
Table of Contents

Advertisement

9 Electro-Magnetic Compatibility (EMC)
9.1.5
Three General classes of EMC performance are available as
detailed below
Class 1: General Industrial
Compliance with the EMC Product Standard for Power Drive Systems EN 68100-3
for use in Second Environment (Industrial) and Restricted Distribution.
Table 9-1
EMC Phenomenon
Emissions:
Radiated Emissions
Conducted Emissions
Immunity:
Electrostatic Discharge
Burst Interference
Radio Frequency Electromagnetic Field IEC 1000-4-3
Class 2: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their
apparatus for compliance with the EMC directive for the industrial environment as
regards the EMC performance characteristics of the power drive system.
Performance limits are as specified in the Generic Industrial Emissions and
Immunity standards EN 50081-2 and EN 50082-2.
Table 9-2
EMC Phenomenon
Emissions:
Radiated Emissions
Conducted Emissions
Immunity:
Supply Voltage Distortion
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
Magnetic Fields
Electrostatic Discharge
Burst Interference
Radio Frequency Electromagnetic
Field, amplitude modulated
Radio-frequency Electromagnetic Field,
pulse modulated
94
Class 1 - General Industrial
Standard
EN 55011
EN 68100-3
EN 61000-4-2
EN 61000-4-4
Class 2 - Filtered Industrial
Standard
EN 55011
EN 55011
IEC 1000-2-4
(1993)
IEC 1000-2-1
EN 61000-4-8
EN 61000-4-2
EN 61000-4-4
ENV 50 140
ENV 50 204
http://nicontrols.com
International English
Level
Level A1
Limits under consideration
8 kV air discharge
2 kV power cables, 1 kV control
26-1000 MHz, 10 V/m
Level
Level A1
Level A1
50 Hz, 30 A/m
8 kV air discharge
2 kV power cables, 2 kV control
80-1000 MHz, 10 V/m, 80% AM, power
and signal lines
900 MHz, 10 V/m 50% duty cycle, 200 Hz
repetition rate
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents