International English
3.2.4.2
Commissioning with the Basic Operator Panel (BOP)
Table 3-1 shows the factory default settings for operation via the Basic Operator
Panel.
Notes
The BOP motor control functions are disabled by default. To control the motor
via the BOP, parameter P0700 should be set to 1 and P1000 set to 1.
The BOP can be fitted to and removed from the inverter whilst power is
applied.
If the BOP has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP is removed.
Table 3-1
Parameter
P0100
P0307
P0310
P0311
P1082
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0
The Basic Operator Panel (BOP) provides access to the
inverter parameters and enables the user to customize
the settings of your MICROMASTER 440. The BOP can
be used to configure several MICROMASTER 440
Inverters. This is accomplished by using the BOP to set
the required parameters and once the process is
complete, then the BOP can be replaced by the SDP.
The BOP contains an five-digit display that allows the user
to read the input and output characteristics of any
parameter. The BOP does not have the capability to store
parameter information.
Default settings for operation using the BOP
Meaning
Operating Mode Europe/US
Power (rated motor)
Motor frequency rating
Motor speed rating
Maximum Motor Frequency
http://nicontrols.com
Default Europe (North America)
50 Hz, kW (60Hz, hp)
Dimension (kW (Hp)) depending on setting of P0100.
[Value depending on variant.]
50 Hz (60 Hz)
1395 (1680) rpm [depending on variant]
50 Hz (60 Hz)
3 Commissioning
39