International English
Fault
Possible Causes
Main supply failed
A0503
Main supply (P0210) and consequently
UnderVoltage
DC-link voltage (R0026) below specified
Limit
limit (P2172).
Warning level of inverter heat-sink
A0504
temperature (P0614) is exceeded,
Inverter
resulting in pulse frequency
OverTemperature
reduction and/or output frequency
reduction (depending on parametrization
in (P0610)
Warning level exceeded, current will be
A0505
2
reduced if parameterized (P0610 = 1)
Inverter I
T
Difference between heatsink and IGBT
A0506
junction temperature exceeds warning
Inverter duty cycle
limits
A0510
Motor
OverTemperature
Motor overloaded.
A0511
Load duty cycle too high.
Motor
OverTemperature
2
I
T
Wire break to motor temperature sensor.
A0512
If a wire breakage is be detected,
Motor temperature
temperature monitoring switches over to
signal lost
monitoring with the motor thermal model.
A0535
Braking Resistor
Hot
Motor data identification (P1910) selected
A0541
or running
Motor Data
Identification
Active
A0600
RTOS Overrun
Warning
CB (communication board) specific
A0700
CB warning 1 see
CB manual for
details.
CB (communication board) specific
A0701
CB warning 2 see
CB manual for
details.
CB (communication board) specific
A0702
CB warning 3 see
CB manual for
details.
CB (communication board) specific
A0703
CB warning 4 see
CB manual for
details.
CB (communication board) specific
A0704
CB warning 5 see
CB manual for
details.
CB (communication board) specific
A0705
CB warning 6 see
CB manual for
details.
CB (communication board) specific
A0706
CB warning 7 see
CB manual for
details.
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0
Diagnose & Remedy
Check main supply voltage (P0210).
Check the following:
1. Ambient temperature must lie within specified
limits
2. Load conditions and duty cycle must be
appropriate
3. Fan must turn when drive is running
Check that duty cycle lies within specified limits
Check that duty cycle and shock loads lie within
specified limits
Check the following:
1. P0611 (motor I
appropriate value
2. P0614 (Motor I
be set to suitable level
See CB user manual
See CB user manual
See CB user manual
See CB user manual
See CB user manual
See CB user manual
See CB user manual