Siemens MICROMASTER 440 Series Operating Instructions Manual page 94

Frequency inverters
Hide thumbs Also See for MICROMASTER 440 Series:
Table of Contents

Advertisement

International English
9.1.4
EMC Directive Compliance with Imminent Harmonics
Regulations
From 1st January 2001 all electrical apparatus covered by the EMC Directive will
have to comply with
EN 61000-3-2 "Limits for harmonic current emissions (equipment input <= 16A per
phase)".
All Siemens variable speed drives of the MICROMASTER, MIDIMASTER,
MICROMASTER Eco and COMBIMASTER ranges, which are classified as
"Professional Equipment" within the terms of the standard, fulfill the requirements
of the standard.
Special considerations for 250W to 550W drives with 230V 1ac mains supplies
when used in non-industrial applications
Units in this voltage and power range will be supplied with the following warning:
"This equipment requires supply authority acceptance for connection to the public
supply network". Please refer to EN 61000-3-12 sections 5.3 and 6.4 for further
information. Units connected to Industrial Networks1 do not require connection
approval (see EN 61800-3, section 6.1.2.2).
The harmonic current emissions from these products are described in the table
below:
Rating
250W 230V 1ac 2.15 1.44 0.72 0.26 0.19 83
370W 230V 1ac 2.96 2.02 1.05 0.38 0.24 83
550W 230V 1ac 4.04 2.70 1.36 0.48 0.36 83
The allowed harmonic currents for "professional equipment" with an input power
>1kW are not yet defined. Therefore, any electrical apparatus containing the
above drives which has an input power >1kW will not require connection approval.
Alternatively, the necessity to apply for connection approval can be avoided by
fitting the input chokes recommended in the technical catalogues (except 550W
230V 1ac units).
1 Industrial Networks are defined as those which do not supply buildings used for domestic purposes.
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0
Typical Harmonic
Typical Harmonic
Current (A)
Current (%)
rd
th
th
th
th
rd
3
5
7
9
11
3
http://nicontrols.com
9 Electro-Magnetic Compatibility (EMC)
Typical Voltage
Distortion
Distribution Transformer
Rating
10kVA
th
th
th
th
5
7
9
11
THD (%) THD (%) THD (%)
56
28
10
7
0.77
56
28
10
7
1.1
56
28
10
7
1.5
100kVA 1MVA
0.077
0.008
0.11
0.011
0.15
0.015
93