Siemens MICROMASTER 440 Series Operating Instructions Manual page 72

Frequency inverters
Hide thumbs Also See for MICROMASTER 440 Series:
Table of Contents

Advertisement

International English
Fault
Possible Causes
Fault caused by the following events:
F0022
(1) dc-link overcurrent = short circuit of
Powerstack fault
IGBT
(2) short circuit of chopper
(3) earth fault
Framesizes A to C (1),(2),(3)
Framesizes D to E (1),(2)
Framesize F (2)
Since all these faults are assigned to one
signal on the power stack, it is not
possible to establish which one actually
occurred.
Fan no longer working
F0030
Fan has failed
MM 440 only
F0040
Automatic
Calibration Failure
Motor data identification failed.
F0041
Alarm value =0: Load missing
Motor Data
Alarm value =1: Current limit level
Identification
reached during identification.
Failure
Alarm value =2: Identified stator
resistance less than 0.1% or greater than
100%.
Alarm value =3: Identified rotorresistance
less than 0.1% or greater than 100%.
Alarm value =4: Identified stator
reactance less than 50% and greater than
500%
Alarm value =5: Identified main reactance
less than 50% and greater than 500%
Alarm value =6: Identified rotor time
constant less than 10ms or greater than
5s
Alarm value =7: Identified total leakage
reactance less than 5% and greater than
50%
Alarm value =8: Identified stator leakage
reactance less than 25% and greater than
250%
Alarm value =9: Identified rotor leakage
inductance less than 25% and greater
than 250%
Alarm value = 20: Identified IGBT on-
voltage less than 0.5 or greater than 10V
Alarm value = 30: Current controller at
voltage limit
Alarm value = 40: Inconsistence of
identified data set, at least one
identification failed
Percentage values based on the
impedance Zb = Vmot,nom / sqrt(3) /
Imot,nom
Read or write failure while saving non-
F0051
volatile parameter.
Parameter
EEPROM Fault
Read failure for power stack information
F0052
or invalid data.
power stack Fault
Read failure for IO EEPROM information
F0053
or invalid data.
IO Eeprom Fault
Internal communications failure
F0060
Asic Timeout
MICROMASTER 440
Operating instructions
6SE6400-5CA00-0BP0
Diagnose & Remedy
Fault cannot be masked while options module (AOP
or BOP) is connected.Need a new fan.
0: Check that the motor is connected to the inverter.
1-40:
Check what type of motor wiring is required (star,
delta).
Factory Reset and new parameterization
Change drive
Change drive
Check data
Change IO module
If fault persists, change inverter
Contact Service Department
http://nicontrols.com
6 Troubleshooting
Check if motor data in P304-311 are correct.
Reac-
tion
Off2
Off2
Off2
Off2
Off2
Off2
Off2
Off2
71