2 Installation
Screening without a Gland Plate
Should a Gland Plate not be available, then the inverter can be screened using the
methodology shown in Figure 2-4.
1
Figure 2-4
Wiring Guidelines to Minimize the Effects of EMI
Legend
1
Mains power input
2
Control cable
3
Motor cable to I/O board
4
Footprint filter
5
Metal back plate
6
Use suitable clips to fix motor and control cable screens securely to metal
back plate
7
Screen cable
Note
To enhance the screening of the motor and control cables, the optional Gland
Plate can be used (not shown in Figure 2-4).
30
5
7
2
4
3
2
MICROMASTER 440
http://nicontrols.com
International English
1
L1
L2
L3
7
6
3
Operating instructions
6SE6400-5CA00-0BP0