Vega VEGAPULS 63 Operating Instructions Manual page 61

Radar sensor for continuous level measurement of aggressive liquids or with hygienic requirements
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.
Byte n
Bit
Bit
Bit
Bit
Bit
Bit
Bit
7
6
5
4
3
2
1
VZ
2
4
2
7
2
6
5
2
2
3
2
Sign
Exponent
Bit
(Exponent - 127)
VZ
2
Value = (-1)
Fig. 40: Data format of the measured value
Coding of the status byte associated with the PA output value
Status
Description according to
code
Profibus standard
0 x 00
bad - non-specific
0 x 04
bad - configuration error
0 x 0C
bad - sensor failure
0 x 10
bad - sensor failure
0 x 1f
bad - out of service constant
0 x 44
uncertain - last unstable value
0 x 48
uncertain substitute set
0 x 4c
uncertain - initial value
0 x 51
uncertain - sensor; conversion
not accurate - low limited
0 x 52
uncertain - sensor; conversion
not accurate - high limited
0 x 80
good (non-cascade) - OK
0 x 84
good (non-cascade) - active
block alarm
0 x 89
good (non-cascade) - active ad-
visory alarm - low limited
0 x 8a
good (non-cascade) - active ad-
visory alarm - high limited
0 x 8d
good (non-cascade) - active crit-
ical alarm - low limited
VEGAPULS 63 • Profibus PA
Byte n+1
Bit
Bit
Bit
Bit
Bit
Bit
Bit
0
7
4
6
5
3
2
2
-3
2
0
2
2
-2
2
-4
2
1
-1
Significant
(1 + Significant)
Possible cause
Flash-Update active
– Adjustment error
– Configuration error with PV-Scale (PV-Span too small)
– Unit irregularity
– Error in the linearization table
– Hardware error
– Converter error
– Leakage pulse error
– Trigger error
– Measured value generation error
– Temperature measurement error
"Out of Service" mode switched on
Failsafe replacement value (Failsafe-Mode = "Last value" and al-
ready valid measured value since switching on)
– Switch on simulation
– Failsafe replacement value (Failsafe-Mode = "Fsafe value")
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
Sensor value < lower limit
Sensor value > upper limit
OK
Static revision (FB, TB) changed (10 sec. active, after the parame-
ter of the static category has been written)
Lo-Alarm
Hi-Alarm
Lo-Lo-Alarm
Byte n+2
Bit
Bit
Bit
Bit
Bit
Bit
7
4
6
5
0
2
1
2
2
2
-9
2
-10 -11 -12 -13 -14 -15 -16 -17
2
-8
2
2
-6
-7
-5
Significant
Bit
Bit
Bit
Bit
Bit
Bit
Bit
0
3
2
1
7
6
5
2
2
2
2
2
2
2
-18 -19 -20 -21 -22 -23
10 Supplement
Byte n+3
Bit
Bit
Bit
Bit
Bit
4
3
2
1
0
2
2
2
2
2
Significant
61

Advertisement

Table of Contents
loading