Vega VEGAPULS 63 Operating Instructions Manual page 40

Radar sensor for continuous level measurement of aggressive liquids or with hygienic requirements
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

6 Set up with the display and adjustment module PLICSCOM
Service - Adjustment unit
Service - Language
Service - HART mode
Copy sensor data
40
Peak value indicator
The min. and max. distance values are reset to the actual value.
In this menu item you select the internal arithmetic unit of the sensor.
Unit of measurement
m(d)
The sensor is already set to the ordered national language. In this
menu item you can change the language. The following languages are
available, e.g. in software version 3.50:
Deutsch
English
Français
Espanõl
Pycckuu
Italiano
Netherlands
Japanese
Chinese
Language
German
HART offers standard and multidrop mode.
The mode standard with the fixed address 0 means output of the
measured value as 4 ... 20 mA signal.
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
5)
In this menu item you determine the HART mode and enter the ad-
dress for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
the operating instructions manual "Display and adjustment module".
The following data are read out or written with this function:
The 4 ... 20 mA signal of the HART sensor is switched off. The sensor
5)
consumes a constant current of 4 mA. The measuring signal is transmitted
exclusively as digital HART signal.