Basic adjustment - Min.
adjustment
VEGAPULS 63 • Profibus PA
6 Set up with the display and adjustment module PLICSCOM
The actual level is then calculated on the basis of these entered
values. At the same time, the operating range of the sensor is limited
from maximum range to the requested range.
Fig. 30: Parameter adjustment example min./max. adjustment
1
Min. level = max. measuring distance
2
Max. level = min. measuring distance
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the thread or flange.
The real product level during this adjustment is not important, be-
cause the min./max. adjustment is always carried out without chang-
ing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Proceed as follows:
1. Move from the measured value display to the main menu by
pushing [OK].
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Select the menu item "Basic adjustment" with [->] and confirm
with [OK]. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3
2
100%
1
0%
31