Advertisement

Parameters menu
4.2

Group 3.2: Start/Stop setup

Index
Parameter
P3.2.1
Remote control place
P3.2.2
Local/Remote
P3.2.3
Keypad stop button
P3.2.4
Start function
P3.2.5
Stop function
P3.2.6
I/O A start/stop logic
P3.2.7
I/O B start/stop logic
P3.2.8
Fieldbus start logic
P3.2.9
Start delay
Remote to Local func-
P3.2.10
tion
* The default value of the parameter depends on the application that is selected with parameter
P1.2 Application. See chapter 10.1 Default parameter values according to the selected application.
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Table 18. Start/Stop Setup menu
Min
Max
Unit
0
1
0
1
0
1
0
1
0
1
0
4
0
4
0
1
0.00
60.00
s
0
2
Default
ID
Description
Selection of remote control
place (start/stop). Can be
used to change back to
remote control from Vacon
0 *
172
Live e.g. in case of a broken
panel.
0=I/O control
1=Fieldbus control
Switch between local and
remote control places
0 *
211
0=Remote
1=Local
0=Stop button always
enabled (Yes)
0
114
1=Limited function of Stop
button (No)
0=Ramping
0
505
1=Flying start
0=Coasting
0
506
1=Ramping
Logic = 0:
Ctrl sgn 1 = Forward
Ctrl sgn 2 = Backward
Logic = 1:
Ctrl sgn 1 = Forward (edge)
Ctrl sgn 2 = Inverted Stop
Ctrl sgn 3 = Bckwrd (edge)
Logic = 2:
1*
300
Ctrl sgn 1 = Forward (edge)
Ctrl sgn 2 = Bckwrd (edge)
Logic = 3:
Ctrl sgn 1 = Start
Ctrl sgn 2 = Reverse
Logic = 4:
Ctrl sgn 1 = Start (edge)
Ctrl sgn 2 = Reverse
1 *
363
See above.
0=Rising edge required
0
889
1=State
The delay between the start
command and the actual
0.00
524
start of the drive can be
given with this parameter.
Choose whether to copy the
Run state and Reference
when changing from
Remote to Local (keypad)
2
181
control:
0 = Keep Run
1 = Keep Run & Reference
2 = Stop
vacon • 89
4