Fault tracing
Fault
Fault
Fault name
code
ID
1315
Temperature
111
fault 1
1316
1317
Temperature
112
fault 2
1318
Pump running
1113
time
113
Pump running
1313
time
700
300
Unsupported
701
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Possible cause
At least one of the selected tempera-
ture input signals (P3.9.6.1) has
reached the alarm limit (P3.9.6.2).
At least one of the selected tempera-
ture input signals (P3.9.6.1) has
reached the fault limit (P3.9.6.3).
At least one of the selected tempera-
ture input signals (P3.9.6.5) has
reached the fault limit (P3.9.6.6).
At least one of the selected tempera-
ture input signals (P3.9.6.5) has
reached the fault limit (P3.9.6.7).
In Multipump system, at least one of
the pump runtime counters has
exceeded a user-defined alarm limit
In Multipump system, at least one of
the pump runtime counters has
exceeded a user-defined fault limit
Unsupported application used.
Unsupported option board or slot used. Remove the option board
vacon • 263
Remedy
Find the cause of temperature
raise.
Check the temperature sensor
and connections.
Check that the temperature
input is hardwired if no sensor
is connected.
See option board manual for
further information.
Carry out the needed mainte-
nance actions, reset the run-
time counter and reset the
alarm. (See ch. 4.15.4)
Carry out the needed mainte-
nance actions, reset the run-
time counter and reset the
fault. (See ch. 4.15.4)
Change the application
9