Ac Input Power For Ns7 Racks; North America/Japan Single-Phase Power Specifications - HP Integrity NonStop X NS7 Planning Manual

Table of Contents

Advertisement

AC Input Power for NS7 Racks

This topic provides power specifications for AC input power in NS7 system racks.
Power Specifications
Region
North America/Japan
International
CAUTION:
the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity. Note that circuit breaker ratings vary if your system includes an optional
rack-mounted UPS.
Table 3 North America/Japan Single-Phase Power Specifications
North America/Japan
Output Load
Input Voltage
Input Connector
Output Voltage
Output Connectors
Notes
Phase
Single-Phase
Three-Phase
Single-Phase
Three-Phase
Be sure the hardware configuration and resultant power loads of each rack within
R5000 1-phase UPS
4500 W
200 – 208 V
NEMA L6-30P
200 – 208 V
1 x L6-30R
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
See...
Table 3 (page 45)
Table 4 (page 46)
Table 5 (page 46)
Table 6 (page 47)
iPDU 1-phase
24 A
200 – 208 V
NEMA L6-30P
N/A
6 x C19
(20 x C13)
AC Input Power for NS7 Racks
Modular PDU 1-phase
24 A
200 – 240 V
NEMA L6-30P
N/A
4 x C19
(28 x C13)
45