Attaching The Pedestal Feet; Connecting Server Cables; Ac Input Power - HP Integrity rx2800 i2 Installation Manual

Hide thumbs Also See for Integrity rx2800 i2:
Table of Contents

Advertisement

Repeat these steps to install the left side piece.

Attaching the pedestal feet

The pedestal feet slide into the slots on the pedestal bottom, two on each side. The feet are all the
same and can be mounted in any slot on the bottom piece of the pedestal kit.
Figure 7 Attaching the feet

Connecting server cables

AC input power

The server can receive AC input from two different AC power sources. The power receptacles are
located at the rear of the server.
A maximum of two power supplies can be installed in the server. Installing two power supplies in
the server provides 1+1 redundancy, meaning that if one power supply fails, there is still enough
power supplied to the server to operate. You must promptly replace the failed power supply to
restore 1+1 functionality.
All high-line (220 V) configurations are capable of 1+1 redundancy. Low-line (1 10 V) configurations
can maintain 1+1 redundancy as long as the total power consumed does not exceed 800 W.
A minimum of one power supply is required to power the server. If only one power supply is
installed in the server, there is no 1+1 capability.
12
Installing the server

Advertisement

Table of Contents
loading

Table of Contents