Adding Refrigerant - Carrier MMY-MAP0724FT9UL Service Manual

Multi type super heat recovery multi-i
Table of Contents

Advertisement

Adding refrigerant

After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging
of refrigerant.
Calculation of additional refrigerant charge amount
Additional refrigerant charge
amount
Table 3
Liquid pipe outer dia.
Additional refrigerant amount/1ft (lbs)
Table 4
Outdoor unit capacity type
072 type
096 type
120 type
144 type
168 type
192 type
216 type
240 type
Example:
(120 type)
L1
L1
Ø1/2": 90ft
a1
Ø1/4": 30ft
a2
Ø1/4": 15ft
Additional charge amount (lbs) =
Selection of installation place
• The cooling performance may decline considerably when total operating capacity of cooling indoor units is
less than 38 kBtu/h while ambient temperature is below 32°F (0°C).
Actual length of liquid
=
(lbs)
pipe
Ø1/4"
0.017
Adjustment amount of refrigerant
(lbs)
5.5
20.9
27.5
5.5
23.1
30.8
34.1
37.4
L3
L2
a1
a2
b2
L2
Ø1/2": 45ft
b1
Ø3/8": 30ft
b2
Ø3/8": 15ft
×
{ (Lx
0.017 lbs/ft)+(Ly
×
=
{ ((a2+d2)
0.017 lbs)+((L3+a1+b1+c1+d1+b2+c2)
×
=
{ (30
0.017 lbs)+(150
=
47.84 lbs
Lx : Actual total length of liquid pipe Ø1/4" (ft)
Ly : Actual total length of liquid pipe Ø3/8" (ft)
Lz : Actual total length of liquid pipe Ø1/2" (ft)
Additional refrigerant charge
×
amount per liquid pipe 1ft
[Table 3]
Ø3/8"
Ø1/2"
Ø5/8"
0.037
0.071
0.108
Combined outdoor units
072 type
096 type
120 type
072 type
096 type
096 type
120 type
120 type
d1
b2
c1
c2
L3
c1
Ø1/4": 15ft
c2
Ø1/4": 15ft
×
×
0.037 lbs/ft)+(Lz
0.071 lbs/ft) }
×
×
×
0.037 lbs)+(135
0.071 lbs) }
– 14 –
Adjustment amount of
×
+
1.3
Ø3/4"
0.168
072 type
072 type
096 type
096 type
120 type
FS unit
d2
Ø3/8":30ft
d1
d2
×
1.3+ 27.5 (lbs)
×
0.037 lbs)+(L1+L2)
0.071 lbs }
×
1.3+27.5 (lbs)
refrigerant
[Table 4]
Ø1/4": 15ft
Ø1/4": 15ft
×
1.3+27.5 (lbs)