Carrier MMY-MAP0724FT9UL Service Manual page 141

Multi type super heat recovery multi-i
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
Detected
outdoor unit
No.
E28
E28
A3-IPDU Fan
1
2
3
IPDU
01
O
02
O
03
O
O
04
O
05
O
O
06
O
O
07
O
O
O
08
O
09
O
O
0A
O
O
0B
O
O
O
0C
O
O
E31
E31
0D
O
O
O
0E
O
O
O
0F
O
O
O
O
80
Symbol O
signifies site of
IPDU error.
80
F01
F02
F03
F04
F04
F05
F05
01:
TE1 sensor error
02:
F06
F06
TE2 sensor error
F07
F07
Location
of
Description
detection
I/F
Outdoor
follower unit
error
I/F
IPDU
Sub
communication
MCU
error
Sub MCU
communication
error
O
Communication
error between MCU
and Sub MCU
Indoor unit
Indoor TCJ
sensor error
Indoor unit
Indoor TC2
sensor error
Indoor unit
Indoor TC1
sensor error
I/F
TD1 sensor error
I/F
TD2 sensor error
I/F
TE1/TE2 sensor
error
I/F
TL sensor error
Error detection
System status
condition(s)
All stop
Outdoor header unit receives
error code from outdoor
follower unit.
All stop
Communication is disrupted
between IPDUs (P.C. boards)
in inverter box.
All stop
Communication between MCU
and Sub MCU stopped.
Stop of
Sensor resistance is infinity or
corresponding
zero (open/short circuit).
unit
Stop of
Sensor resistance is infinity
corresponding
or zero (open/short circuit).
unit
Stop of
Sensor resistance is infinity
corresponding
or zero (open/short circuit).
unit
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
– 141 –
Check items (locations)
• Check check code displayed
on outdoor follower unit.
<Convenient functions>
If SW04 is pushed and held for
at least 1 second while [E28] is
displayed on the 7-segment
display of outdoor header unit,
the fan of the outdoor unit that
has been shut down due to an
error comes on.
If SW04 and SW05 are pushd
simultaneously, the fans of
normal outdoor units come on.
To stop the fan or fans, push
SW05 on its own.
• Check wiring and connectors
involved in communication
between IPDU-I/F P.C. board
for bad contact or broken wire.
• Check for defect in outdoor
P.C. board (I/F, A3-IPDU or
Fan IPDU).
• Check for external noise.
• Operation of power supply
reset (OFF for 60 seconds
or more)
• Outdoor I/F PC board error
check
• Check connection of TCJ
sensor connector and wiring.
• Check resistance
characteristics of TCJ sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC2
sensor connector and wiring.
• Check resistance
characteristics of TC2 sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TC1
sensor connector and wiring.
• Check resistance
characteristics of TC1 sensor.
• Check for defect in indoor
P.C. board.
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2 sensor.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL sensor.
• Check for defect in outdoor
P.C. board (I/F).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents