10-3.Backup Setup for Outdoor Unit

Outline
In this model, setup of the backup operation is available in either the header unit or the follower unit in a
situation where the outdoor units are defective. In a system in which two or more outdoor units are connected,
carry out the backup operation on the outdoor unit if the error modes described below occur.
• Compressor error (Rare short error or when one compressor cannot operate, etc.)
• Pressure sensor (Pd, Ps) / Temperature sensor (TD1, TD2, TD3, TS1, TS2, TE1, TE2, TK1, TK2, TK3, TK4,
TK5, TL) error
Note only one outdoor unit within a given system can be subjected to the backup procedure.
Procedure
(1) Turn off the main power supplies to all the units connected to the system.
[Set up procedure for the malfunctioning outdoor unit]
(The following work is common to the header unit and follower units in the system.)
(2) Set the DIP switches of SW06, provided on the interface P.C. board of the outdoor unit with the faulty
compressor, as shown in the table below.
Factory default setting
Outdoor unit backup
Factory default setting
Outdoor unit backup
(3) When there is leakage of outdoor PMV (does not close) or a trouble, close the liquid valve service valves fully.
(4) Turn on the power supply to all the units connected to the system.
When a trouble due to insufficient insulation, etc. occurred, remove in advance lead wire of the compressor.
This is the end of compressor backup operation setting.
Three-compressor model
Two-compressor model
SW06
SW07
1 2 3 4
1 2 3 4
1 2 3 4
SW11
SW12
1 2 3 4
1 2 3 4
1 2 3 4
SW16
SW17
1 2 3 4
1 2 3 4
SW06
Bit 1
Bit 2
OFF
OFF
ON
ON
SW06
Bit 1
Bit 2
OFF
OFF
ON
ON
– 209 –
SW09
SW10
1 2 3 4
SW13
SW14
1 2 3 4
Bit 3
Bit 4
OFF
OFF
ON
OFF
Bit 3
Bit 4
OFF
OFF
OFF
OFF