3-2. Outdoor Unit
(460V model: MMY-MAP
No.
Parts Name
1 Compressor
2 4-way valve coil
3 PMV coil
4 2-way valve coil
5 2-way valve coil
6 2-way valve coil
7 2-way valve
8 2-way valve
9 2-way valve
10 2-way valve
11 2-way valve
12 High-pressure SW
13 Pressure sensor
(For high pressure)
14 Pressure sensor
(For low pressure)
15 Fan motor
16 Case heater (For comp.)
17 Case heater (For accum.)
18 Fusible plug
∗∗∗
4FT6UL)
Model
DA421A3FB-29M1
STF-01AQ1839UA1
HAM-MD12TF-6
VPV-MOAQ1843A0
SV3A
SV3B
SV3C
SV3D
SV3E
SV3F
FQ-D640
SV41
SV42
SV43
SR53 AC200L1500
SV11
SV14
VPV-303DQ1
SV3E
SV3F
VPV-603DQ2
SV3B
FDF3A06
SV41
SV42
SV43
VPV-122DQ1
SV3A
SV3C
SV3D
SV3E
SR53-04WR BA
SV11
SV14
ACB-4UB3
NSK-BC038F-U22
NSK-BC010F-U22
STF-340A1000-1
Specification
Output: 2.3kW × 2
Output: 2.1kW × 3
Output: 2.7kW × 3
AC208 ~ 230V, 60Hz
DV12V
SV2
AC208 ~ 230V, 60Hz
SV6
AC208 ~ 230V, 60Hz
SV5
AC208 ~ 230V, 60Hz
SV5
SV2
SV6
OFF : 540psi (3.73MPa)
ON : 420psi (2.9MPa)
0.5~4.3V/0~540psi (3.73MPa)
0.5~3.5V/0~142psi (0.98MPa)
DC280V/1kW
AC240V/29W
AC240V/55W
163.4˚F (73˚C)
– 32 –
MMY-MAP
072
096
120