Carrier MMY-MAP0724FT9UL Service Manual page 233

Multi type super heat recovery multi-i
Table of Contents

Advertisement

No. Part to be replaced
6-2
Reactor assembly
(460V FT6UL)
Work procedure
WARNING
Wear gloves.
Failure to wear gloves creates the risk of
personal injury by part replacement and
other objects.
1) Stop operation and turn off the breaker switch.
2) Remove the inverter assembly.
(Refer to "4. Removing the inverter assembly".)
3) For 096 and 120 only, remove the separate
reactor box.
Remove the upper and lower screws (M5 x 0.4"
(10 mm)), slide the claw to the right, and then
remove the reactor box.
* Swing the reactor box upwards, slip it
downwards, and then pull it out.
4) Remove the reactor box, which is behind the inverter
assembly.
(M4 × 0.2" (6 mm), 4 pcs)
* Remove the screws starting from the front.
For 096 and 120, remove the separate anchor plate.
(M4 × 0.2" (6 mm)6, 4 pcs)
5) Remove the reactor and replace it.
(M4 × 0.2" (6 mm)6, 1 pc)
• 096type, 120type
• 072 type
– 233 –
Remarks
3) Screw
Claw (Slide to the right.)
3) Screw
Claw (Slide to the right.)
4) Screw (2 locations)
4) Screw (2 locations)
4) Screw (2 locations)
4) Screw (2 locations)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents