No. Part to be replaced
6-1
Reactor assembly
(208/230 V FT9UL)
Work procedure
WARNING
Wear a pair of gloves.
Otherwise, you will risk an injury involving
a replacement part or some other object.
1. Detachment
1) Stop the operation, and turn off the circuit breaker.
2) Remove the inverter assembly.
(See the inverter assembly dismantling method
under item 5.)
3) For 096 and 120 only, remove the separately
mounted reactor box.
To remove the reactor box, remove the screws at
the top and bottom (M5 × 0.4" (10 mm)) and
unlock the box by sliding the stopper to the right.
* Before pulling the reactor box, tilt it back to free
the bottom.
4)Remove the reactor box located at the back of the
inverter assembly.
(M4 × 0.2" (6 mm), 4 pcs.)
* The screws can be removed from the front.
For 096 and 120 only, remove the separately
mounted anchor plate.
(M4 × 0.2" (6 mm), 4 pcs.)
5) Remove and replace the reactor.
(M4 × 0.2" (6 mm), 1 pc.)
– 231 –
Remarks
• 096 type, 120 type
3) Screw
Fixing claw (slide stopper to right)
Screw
3)
Fixing claw (slide stopper to right)
4) Screws (2 locations)
4) Screws (2 locations)
• 072 type
4) Screws (2 locations)
4) Screws (2 locations)