Carrier MMY-MAP0724FT9UL Service Manual page 146

Multi type super heat recovery multi-i
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
L02
L02
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
L10
L10
L20
L28
L28
A3-IPDU Fan
1
2
3
01
O
02
O
03
O
O
04
O
05
O
O
06
O
O
07
O
O
O
08
L29
L29
09
O
0A
O
0B
O
O
0C
O
0D
O
O
0E
O
O
0F
O
O
O
Symbol O
signifies site of
IPDU error.
Detected indoor
address
L30
L30
Location
of
Description
detection
Indoor unit
Outdoor units
model
disagreement
error
Indoor unit
Duplicated
indoor header
unit
I/F
Duplicated
outdoor line
address
I/F
Duplicated priority
indoor unit
(as displayed on
priority indoor unit)
I/F
Duplicated priority
indoor unit
(as displayed on
indoor unit other
than priority
indoor unit)
Indoor
Connection of
unit
group control
cable to stand-
alone indoor unit
Indoor
Indoor group /
unit
addresses not
set
Indoor unit
Indoor capacity
not set
I/F
Outdoor capacity
not set
Indoor unit
Duplicated
central control
address
I/F
Too many
outdoor units
connected
I/F
Error in No. of
IPDUs
IPDU
O
O
O
O
O
O
O
O
Indoor unit
External interlock
of indoor unit
Error detection
System status
condition(s)
Stop of
In case of different outdoor unit. • Check outdoor unit model.
corresponding
unit
Stop of
There is more than one header
corresponding
unit in group.
unit
All stop
There is duplication in line
address setting for outdoor
units belonging to different
refrigerant piping systems.
All stop
More than one indoor unit has
been set up as priority indoor
unit.
All stop
More than one indoor unit
have been set up as priority
indoor unit.
Stop of
There is at least one stand-
corresponding
alone indoor unit to which group
unit
control cable is connected.
Stop of
Address setting has not been
corresponding
performed for indoor units.
unit
Stop of
Capacity setting has not been
corresponding
performed for indoor unit.
unit
All stop
Jumper wire provided on P.C.
board for servicing I/F P.C.
board has not been removed as
required for given model.
All stop
There is duplication in central
control address setting.
All stop
There are more than 2
outdoor units.
All stop
Insufficient number of IPDUs
are detected when power is
turned on.
Stop of
• Signal is present at external
corresponding
error input terminal (CN80) for
unit
1 minute.
– 146 –
Check items (locations)
• Check indoor addresses.
• Check for any change made
to remote controller
connection (group/individual)
since indoor address setting.
• Check line addresses.
• Check display on priority
indoor unit.
• Check displays on priority
indoor unit and outdoor unit.
• Check indoor addresses.
• Check indoor addresses.
Note:
This code is displayed when
power is turned on for the
first time after installation.
Set indoor capacity. (DN = 11)
Check model setting of P.C.
board for servicing outdoor I/F
P.C. board.
• Check central control
addresses.
• Check No. of outdoor units
connected (Only up to 2 units
per system allowed).
• Check communication lines
between outdoor units.
• Check for defect in outdoor
P.C. board (I/F).
• Check model setting of
P.C. board for servicing
outdoor I/F P.C. board.
• Check connection of UART
communication connector.
• Check A3-IPDU, fan IPDU,
and I/F P.C. board for defect.
When external device is
connected to CN80
connector:
1) Check for defect in external
device.
2) Check for defect in indoor
P.C. board.
When external device is not
connected to CN80
connector:
1) Check for defect in indoor
P.C. board.