Note 1: Criteria for the difference between suction and discharge temperatures
(1) Individual cooling operation
After operating for a minimum of 30 minutes in "COOL" mode, if the ΔT dry bulb temperature difference
between suction and discharge air of the indoor unit is 46.4°F (8°C) or more, it is normal.
(2) Individual heating operation
After operating for a minimum of 30 minutes in "HEAT" mode, if the ΔT dry bulb temperature difference
between suction and discharge air of the indoor unit is 59°F (15°C) or more, it is normal.
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature
set by the remote controller and the temperature of the room is small, then the ΔT temperature difference
is small.
* Consider that ΔT temperature difference may diminish in cases of a system in which the connected indoor
unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among
outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating
current is about 80% of the value shown in the table below.
Outdoor unit
MMY-MAP
current valve
(A)
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Cassette type air conditioner of 100% connection with
standard piping length.
Data may vary depending on temperature conditions, installed pipe length, and room shape combinations,
or indoor unit connection capacity.
For pressure criteria in different temperature conditions, refer to (2).
Pressure (psi)
Model
Operating
MMY-MAP
mode
Pd
All cooling
410
0724FT9UL
/ 0724FT6UL
All heating
428
All cooling
415
0964FT9UL
/ 0964FT6UL
All heating
430
All cooling
421
1204FT9UL
/ 1204FT6UL
All heating
435
* This compressor is driven with a 4-pole motor. The value of the compressor frequency (rps) measured with a
clamp meter at the compressor lead line is two times the rotation count (rps) of the compressor.
* Each compressor may have a different frequency as a measure against resonance.
* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and
TC2 sensor temperature when heating, respectively.
(2) Criteria for operating pressure
Operating mode
Indoor temp.
Outdoor temp.
Pd
Pressure
Ps
* Criteria after 15 minutes or more has passed since operating started.
(3) On rotations of outdoor fans
Outdoor fans may rotate slowly to control pressure when cooling with low outer air temperature or heating
with excessive load. For control content, also refer to items in Section 5, "Control Outline: Outdoor Unit,
Outdoor Fan Control."
0724FT9UL
0964FT9UL
34
50
Pipe surface temperature (˚F)
Discharge
Suction 1
Suction 2
Ps
(TD)
(TS1)
(TS2)
130
183
82
59
102
184
39
40
130
184
83
60
102
186
37
38
130
186
84
60
100
184
37
39
All cooling
All heating
(˚F)
64 – 90
(˚F)
77 – 95
(psi)
290 – 465
365 – 475
(psi)
75 – 135
1204FT9UL 0724FT6UL 0964FT6UL 1204FT6UL
52
Indoor
Outdoor
Liquid
heat
heat
temperature
exchanger
exchanger
(TL)
(TC)
(TE)
48
105
102
100
38
90
48
105
102
100
36
91
50
105
102
101
36
91
59 – 77
41 – 50
70 – 110
– 111 –
19
28
Number of compressor rotations (rps)*
Compressor
Compressor
Compressor
1
2
50
50
50
50
45
45
50
50
50
50
57
57
30
Air temperature
Indoor
condition
(DB/WB)(˚F)
fan
3
Indoor Outdoor
High
80/67
95/—
High
70/—
47/43
45
High
80/67
95/—
50
High
70/—
47/43
50
High
80/67
95/—
57
High
70/—
47/43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents