Carrier MMY-MAP0724FT9UL Service Manual page 88

Multi type super heat recovery multi-i
Table of Contents

Advertisement

NOREQUIREMENTE
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the
group before setting addresses.
• If you set the unit addresses of each line separately, each line's header indoor unit is set separately. In that
case, the CODE No. "L03" (Indoor header unit overlap) is indicated as running starts. Change the group
address to make one unit the header unit using wired remote controller.
(Example)
System wiring
diagram
Address setting procedure 2
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board on
the header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant
line) or DI/SDI series.
Interface P.C. board on the header outdoor unit
Line address switches on the outdoor interface PC board (
Line
address
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Controlling 2 or more refrigerant lines as a group
Outdoor
Indoor
Indoor
(Group control)
Remote
controller
SW06
SW07
1 2 3 4
1 2 3 4
SW11
SW12
1 2 3 4
1 2 3 4
SW13
SW14
2
3
4
1
2
×
×
×
×
×
O
×
×
O
×
O
O
×
×
×
×
×
O
×
×
O
×
O
O
×
×
×
×
×
O
×
×
O
×
O
O
×
×
×
×
×
O
Not used for setup of line address (do not change setup.)
Outdoor
Indoor
Indoor
SW09
SW10
1 2 3 4
1 2 3 4
SW13
SW14
1 2 3 4
1 2 3 4
: switch on,
O
Line
address
3
4
×
×
15
×
×
16
×
×
17
×
×
18
×
19
O
×
20
O
×
21
O
×
22
O
×
23
O
×
24
O
×
25
O
×
26
O
27
O
O
28
O
O
– 88 –
×
: switch off)
SW13
1
2
3
4
1
×
×
×
O
×
O
O
O
×
O
O
O
×
O
O
O
×
O
O
O
×
O
O
O
×
O
O
O
SW14
2
3
4
O
O
O
O
O
O
×
×
×
×
×
×
×
×
O
×
×
O
×
×
O
×
×
O
×
O
O
×
O
O
×
×
O
×
×
O
×
O
O
×
O
O

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents