Particulate And Gaseous Contamination Specifications - Dell PowerEdge R730xd Owner's Manual

Hide thumbs Also See for PowerEdge R730xd:
Table of Contents

Advertisement

Table 24. Relative humidity specifications
Relative humidity
Storage
Operating
Table 25. Maximum vibration specifications
Maximum vibration
Operating
Storage
Table 26. Maximum shock specifications
Maximum vibration
Operating
Storage
Table 27. Maximum altitude specifications
Maximum altitude
Operating
Storage
Table 28. Operating temperature de-rating specifications
Operating temperature de-rating
Up to 35°C (95°F)
35°C to 40°C (95°F to 104°F)
40°C to 45°C (104°F to 113°F)

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from
particulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed the
specified limitations and result in equipment damage or failure, you may need to rectify the
Specifications
5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
10% to 80% relative humidity with 29°C (84.2°F) maximum
dew point.
Specifications
0.26 G
at 5 Hz to 350 Hz (all operation orientations).
rms
1.88 G
at 10 Hz to 500 Hz for 15 min (all six sides
rms
tested).
Specifications
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes of 40 G for up to 2.3 ms.
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Specifications
3048 m (10,000 ft)
12,000 m (39,370 ft)
Specifications
Maximum temperature is reduced by 1°C/300 m (1°F/547
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/175 m (1°F/319
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1°C/125 m (1°F/228
ft) above 950 m (3,117 ft).