Removing A Dc Power Supply Unit - Dell PowerEdge R730xd Owner's Manual

Hide thumbs Also See for PowerEdge R730xd:
Table of Contents

Advertisement

Removing a DC power supply unit

Prerequisites
WARNING: For equipment using –(48–60) V DC power supply units (PSUs), a qualified electrician
must perform all connections to DC power and to safety grounds. Do not attempt connecting to
DC power or installing grounds yourself. All electrical wiring must comply with applicable local
or national codes and practices. Damage due to servicing that is not authorized by Dell is not
covered by your warranty. Read and follow all safety instructions that came with the product.
CAUTION: The system needs one power supply for normal operation. On power-redundant
systems, remove and replace only one power supply at a time in a system that is powered on.
NOTE: You may have to unlatch and lift the optional cable management arm if it interferes with
power supply removal. For information about the cable management arm, see the rack
documentation of your system.
Steps
1.
Disconnect the power wires from the power source and the connector from the PSU you intend to
remove.
2.
Disconnect the safety ground wire.
3.
Press the release latch and slide the PSU out of the chassis by using the PSU handle.
Figure 84. Removing a DC PSU
1.
release latch
3.
PSU
5.
PSU handle
166
2.
power supply status indicator
4.
power connector

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents