10. Maintenance & Inspection
Never touch the internal parts.
Failure to obey may result in electrical shock, personal injury and other dangers.
Careful checking and maintenance are essential to ensure that the general-purpose inverter SVC06 series can operate
correctly with a long service life.
10-1 Precautions on Checking and Maintenance
Capacitors retain a high voltage charge for a while after the power is turned off. Before carrying out
inspection, please firstly make sure that the CHARGE lamp is off, then make sure that the voltage across
terminals P and X is lower than DC30V using a circuit tester.
10-2 Inspection Items
The motor works as expected;
The cooling system is free from any problems (such as abnormal heating);
There is no abnormality at the location of installation; and
There is no abnormal vibration or noise.
Table 10-1
Inspection must be carried out following the periodic inspection list.
Inspection item
Ambient
environment
Power supply
voltage
Appearance
Structural parts
General
Connection
conductors
and wires
Main module
Table 10-1
Inspection details
Ambient temperature, relative
humidity
Confirm operating environment
Power supply voltage of the
inverter is normal.
No abnormal vibration or noise
No loosening of bolts
No deformation or breakage
No adhesion of dust or dirt
Megger check
No loosening of bolts
No adhesion of dust or dirt
No deformation or dirt
No discoloration because of
overheating
Check resistance between
terminals
Periodic inspection list
Method & Instrument
Visual inspection, measuring
instrument
Thermometer & hygrometer
Measure interphase voltage
of R, S and T input
terminals.
Use tester and multimeter
Tighten bolts
Visual inspection
Tighten bolts
Visual inspection
Visual inspection
Disconnect the main wiring
of the inverter and measure
each terminal with tester (x1
range)
Use analog tester
- 300 -
Criteria
Satisfy standard
specifications
Satisfy standard
specifications of input
No abnormal
No abnormal
No abnormal
Refer to Table 10-2 Main
circuit power module
checklist