7-3
Description of Functions
F1507

Arrival frequency

This function specifies the frequency at which a frequency arrival signal is output.
Code No.
Function Name
F1507
Arrival frequency
If the value of any one of F1509 – F1511 is 7 (frequency arrival), the signal is output from control circuit output terminals
DO1 to DO3 when the output frequency exceeds the value of F1507.
Similarly, If the value of F1513 is 7 (frequency arrival), the signal is output from control circuit relay output terminals
FA1, FB1 or FC1 when the output frequency exceeds the value of F1507.
Frequency arrival signal
F1508

Frequency matching range

This function specifies the out frequency band corresponding to the frequency matching signal.
Code No.
Function Name
F1508
Frequency matching range
If the value of any one of F1509 – F1511 is 5, 6, 14 or 15, the signal is output from control circuit terminals DO1 to DO3
when the output frequency falls within the value range between ±F1508.
Similarly, for F1513, the signal is output from control circuit relay output terminals FA1, FB1 or FC1.
Note: When the frequency is specified using an analog signal, an appropriate setting should be specified using F1508 to
prevent frequency matching signal from chattering. When the vector control is active, the output frequency
constantly changes. Set F1508 to several Hz.
0-600Hz
Output
frequency
F1507: Arrival frequency setting value
0-10Hz
Data Content
Data Content
- 154 -
Setting
Factory Presets
Resolution
0.01Hz
10
Time
Setting
Factory Presets
Resolution
0.01Hz