Mbs Terminal Input Mode - Sanken SVCO6 Instruction Manual

Table of Contents

Advertisement

Code No.
Function Name
F1411
Analog input switching for
set frequency gain
● When several inverters are used for proportional operation, this function is useful for fine adjustment of the
command frequencies of the inverters from the master to the slave.
● The external analog input terminal is switched with F1411 (Analog input switching for set frequency gain).
● Use F1410 as the set frequency value for proportional operation.
Example 2) When the set frequency is 50Hz, F1410 = 50%, if the external analog input is 0 - 10V
·
0V: 50Hz - (50Hz × 50%) = 25Hz.
·
5V: 50Hz - (50Hz × 0%) = 50Hz.
·
10V: 50Hz + (50Hz × 50%) = 75Hz.
F1412

MBS terminal input mode

This function is used to select the input signal action of multifunction input terminal MBS.
Code No.
Function Name
F1412
MBS terminal input mode
Edge operation will accept MBS input once between OFF and ON
Data Content
0: No analog input
1: External analog VIF1 voltage (0-5V)
2: External analog VIF1 voltage
(0-10V or potentiometer)
3: External analog VIF2 voltage (0-5V)
4: External analog VIF2 voltage
(0-10V or potentiometer)
5: External analog VIF3 voltage (0-5V)
6: External analog VIF3 voltage
(0-10V or potentiometer)
7: External analog VIF1 current
(4-20mA)
8: External analog VIF2 current
(4-20mA)
9: External analog VIF3 current
(4-20mA)
VIF1 or VIF2 or VIF3 input
Data Content
1: Level triggered
2: Edge triggered
- 143 -
7-3
Description of Functions
Setting
Factory Presets
Resolution
1
0
Setting
Factory Presets
Resolution
1
1