burner and making
soot.
7. When I turn on my
fireplace, there are long
blue flames coming off
the burner and the
fireplaces stops
working after a minute.
8. I smell gas.
9. My remote control
cannot turn off the
fireplace.
10. When I turn my
fireplace off, the pilot
light remains lit.
11. A lot of soot is
accumulating on the
inner walls of the
fireplace.
12. The flame intensity
varies.
75
6B. Air restrictor is not open
enough.
6C. Vent is blocked or defective.
7A. Not enough air intake.
7B. Gas exhaust panel is not open
enough.
7C. Vent is blocked or defective.
9A. Batteries in the remote control
are dead.
9B. You are too far from the
fireplace.
9C. A component of the
defective.
10A. Your fireplace is in CPI mode.
11A. The exhaust panel is not open
enough and causes poor
combustion.
11B. The vent is blocked
12A Your fireplace is in thermostat
mode
adjust as described in section
4.1.
6B: Adjust gas intake and exhaust
properly as described in section
4.1.
6C: Contact a certified technician to
have your vent ducts inspected.
7A: Start by checking the air/gas
premix adjustment screw and
adjust as described in section
4.1.
7B. Adjust gas intake and exhaust
properly as described in section
4.1.
7C: Contact a certified technician to
have your vent ducts inspected.
8B. Refer to the front page of this
manual immediately and follow
instructions
9A. Change the batteries in the
remote control.
9B. Move closer to the fireplace.
9C. Close the manual valve
upstream from the fireplace and
®
SmartCase
is
call your J. A. ROBY retailer.
10A. Refer to section 4.2.2 to set
the remote control in IPI mode.
11A. Refer to section 4.1 to adjust
the gas exhaust panel in a
more open position.
11B: Contact a certified technician
to have your vent system
inspected.
12A. Refer to section 4.2.2 to
deactivated thermostat mode