Lighting The Appliance; Checking For Clearance Of - Flavel EmberGlow Classic FEMC00EN Installation, Maintenance & User Instructions

Battery ignition radiant convector gas fire
Table of Contents

Advertisement

Refit the Front Casting, which locates onto the the two fixing screws.
Note: It is important that the decorative Front Casting is fitted before
attempting to use the fire.
3.2

Lighting the Appliance

a)
Light the pilot by depressing the control knob at the "off" position and
turn anti-clockwise (with the control depressed) to the second position
marked *.
b)
When the pilot lights, (pilot can be seen through the right hand side
window, between the fuelbed base and coals) hold the control knob
down for 10 seconds.
c)
If the pilot fails to light, repeat the ignition sequence and hold in the
control knob for slightly longer.
d)
When the pilot has lit, release the control knob from the depress
position, depress slightly again and turn the control anti-clockwise to the
high position and check for clearance of combustion products as
detailed below.
IMPORTANT: THE FIRE MUST ONLY BE OPERATED WITH THE
FRONT CASTING IN PLACE
3.3
Checking for Clearance of Combustion Products
a)
Close all doors and windows in the room.
b)
Light the fire and turn to the maximum position.
After 5 minutes hold the smoke match as shown in Fig. 14 overpage.
Whilst holding the smoke match in the correct position, approximately
25mm below the lower edge of the draught diverter.
Ensure that most of the smoke is drawn into the flue aperture. If in
doubt repeat the exercise after a further 5/10 minutes.
Note:-
It is recommended that the smoke match is fitted into an approved
smoke match holder, when checking for clearance of combustion
products.
17