General Access For Servicing - Flavel EmberGlow Classic FEMC00EN Installation, Maintenance & User Instructions

Battery ignition radiant convector gas fire
Table of Contents

Advertisement

Servicing Notes
Servicing should be carried out annually by a competent person such as a
Gas Safe registered engineer.
The service should include visually checking the chimney and fire opening for
accumulations of debris and a smoke test to check for positive up-draught in
the chimney.
The condition of the fuelbed ceramics & coals should be checked and if
necessary the whole set should be replaced with a genuine replacement set.
After any servicing work a gas tightness check must always be carried out.
4.1

GENERAL ACCESS FOR SERVICING

4.1.1
TO REMOVE THE UPPER CANOPY / GLASS PANEL
a)
Prepare work area (lay down dustsheets etc.), Disconnect the appliance
from the gas supply.
b)
Remove the four canopy rear fixing screws, as decribed on page 11
(fig. 5)
c)
Remove the glass front panel as descibed on page 9, (fig. 2)
d)
Re-assemble in the reverse order.
4.2
REMOVING THE BURNER ASSEMBLY FROM THE FIRE
a)
Prepare work area (lay down dustsheets etc.), Disconnect the appliance
from the gas supply.
b)
Remove the four canopy rear fixing screws, as decribed on page 11
(fig. 5)
c)
Remove the glass front panel as descibed on page 9, (fig. 2)
d)
Remove the pilot retaining screws as shown below in fig. 15
Fig. 15
MAINTENANCE INSTRUCTIONS
19
2 off ODS Pilot
Retaining
Screws