Toshiba MD-VNK802HEXE Service Manual page 55

Table of Contents

Advertisement

Check code list (Outdoor)
(Example: Detected on the SMMS-i standard & thermal outdoor interface)
Check code
7-segment display of outdoor unit
Sub code
Number of indoor units for normal
E06
reception
E07
E08 Duplicate indoor unit No.
01: Central control
E12
02: Communications between
outdoor units
E15
00: Over capacity
E16
01 ~: Number of connected units
00: No center unit
E19
02: Multiple center units
01: Outdoor connections of another
line
E20
02: Indoor connections of another
line
00: Number of duplicate header
E21
units
02: No header unit
E22
E23
E25
Outdoor address with reception
E26
error
E28 Detected outdoor unit No.
A3-IPDU
A3-IPDU
Fan
IPDU
1
2
3
1
2
01 O
0A
O
02
O
0B O O
03 O O
0C
E31
04
O
0D O
05 O
O
0E
O O
06
O O
0F O O O
07 O O O
O: IPDU error
08
O
09 O
O
F04
F05
01: TE1
F06
02: TE2
F07
F08
F11
F12
F15
F16
Local remote
Typical cause of error
controller &
TCC-LINK
central controller
E06
Number of indoor units decreasing
(E04)
Central communication circuit error
(E08)
Duplicate indoor addresses
E12
Automatic address start error
No indoor unit during automatic
E15
address
Number of connected units /
E16
Capacity exceeded
Unusual number of center outdoor
E19
units
Connections of another line during
E20
automatic address
Unusual number of thermal header
E21
units
E22
Number of thermal units decreasing
Transmission error between
E23
outdoor units
Duplicate terminal outdoor address
E25
settings
Number of connected outdoor units
E26
decreasing
E28
Terminal outdoor error
Fan
IPDU
3
O
O
O
O
O
O
E31
IPDU communication error
O
O
Outdoor discharge temperature
F04
sensor (TD1) error
Outdoor discharge temperature
F05
sensor (TD2) error
Outdoor heat exchange
F06
temperature sensor (TE1, TE2)
error
Outdoor liquid temperature sensor
F07
(TL) error
Outdoor temperature sensor (TOA)
F08
error
F11
Outdoor suction temperature
F12
sensor (TS1) error
Miswiring of outdoor temperature
F15
sensor (TE1, TL) error
Miswiring of outdoor pressure
F16
sensor (Pd, Ps) error
No communication can be established any more. (The number of
connected indoor units has decreased.)
No signal can be sent to the indoor unit. (No communications from
outdoor unit to indoor unit)
There are multiple indoor units with the same address. (May also
be detected on the indoor unit)
The automatic indoor address operation has been performed
during automatic address setting of another line.
The automatic outdoor address operation has been performed
during indoor automatic address setting.
No data is received from the outdoor unit during automatic
address.
The total capacity of indoor units has been exceeded. (Over 135 %
of total capacity of outdoor unit)
There are no or multiple center outdoor units in a line.
An indoor unit of another line has been detected during automatic
address setting.
There are no or multiple thermal header units in a line.
No communication can be established any more. (The number of
connected thermal units has decreased.)
No signal can be sent to another outdoor unit.
The manually set terminal outdoor addresses are duplicate.
No communication can be established any more. (The number of
connected terminal outdoor units has decreased.)
The center outdoor unit has detected an error of the terminal
outdoor unit. (Details displayed for the terminal outdoor unit)
There is no communication of each IPDU (PC board) in the inverter
box.
Open-circuit or short-circuit of the outdoor discharge temperature
sensor (TD1) was detected.
Open-circuit or short-circuit of the outdoor discharge temperature
sensor (TD2) was detected.
Open-circuit or short-circuit of the heat exchange temperature
sensor (TE1, TE2) was detected.
Open-circuit or short-circuit of the outdoor liquid temperature
sensor (TL) was detected.
Open-circuit or short-circuit of the outdoor temperature sensor
(TOA) was detected.
Open-circuit or short-circuit of the outdoor suction temperature
sensor (TS1) was detected.
Miswiring of the temperature sensor (TE1, TL) was detected.
Miswiring of the outdoor pressure sensor (Pd, Ps) was detected.
53
Description

Hide quick links:

Advertisement

Table of Contents
loading